F706
Display Bias
Program Utilities Display Parameters
In conjunction with the setting of F702, this parameter sets the bias of the front
panel speed display.
The frequency entered here will be multiplied by the setting of
displayed as the zero value on the front panel display.
Change Step Selection 1
Program Utilities Display Parameters
In conjunction with the parameter setting of F708, this parameter sets the
amount that the output speed will increase or decrease for each speed command
change entered from the front panel using the Rotary Encoder.
Change Step Selection 2
Program Utilities Display Parameters
The parameter is used to modify the degree that the setting of
output speed changes that are input from the front panel using the Rotary
Encoder.
Selecting a zero value here disables this parameter and the resulting non-zero
value of parameter setting
F707
Selecting a non-zero value here provides a dividend that will be used in the
following equation resulting in the actual output frequency applied to the motor.
OutputFrequencyDisplayed
Operation Command Clear Selection When ST Off
Program Special  Operation Panel Parameters
Upon deactivation of the ST terminal while operating in the Local mode, the
ASD output to the motor will cease — this parameter setting is used to allow
for the reactivation of the motor without user intervention upon the reactivation
of the ST terminal.
Upon reactivation of the ST terminal in this condition the ASD will resume the
Run condition and the motor will start (1 — Retain Run Command).
This feature may be Disabled and the Run command must be re-initiated by the
user for ASD operation (0 — Clear Panel Run Command).
DANGER
WHEN ENABLED THE ASD WILL RESUME THE RUN CONDITION
WHEN THE ST TERMINAL IS REACTIVATED.
Settings:
0 — Clear Panel Run Command
1 — Retain Panel Run Command
198
F702
F707
is output from the ASD.
=
InternallyCommandedFrequency
Direct Access Number — F706
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
and then
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F707
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F708
Parameter Type — Numerical
Factory Default — 0 (Disabled)
affects the
Changeable During Run — Yes
Minimum — 0
Maximum — 255
F708
------------ -
F707
Direct Access Number — F719
Parameter Type — Selection List
Factory Default — Retain Panel Run
Command
Changeable During Run — Yes
G9 ASD Installation and Operation Manual
F719