Toshiba G9 Installation And Operation Manual page 47

Asd
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
Command Control Selections
The following is a listing with descriptions of the
Command Mode (F003) selections (Program 
Fundamental  Standard Mode Selection  Command
Mode Selection).
Settings:
0 — Terminal Block
Allows for Command control input via the
Terminal Board.
1 — Not Used
Unused.
2 — EOI Keypad
This setting is used for EOI command control.
3 — RS485
This setting is used to transfer commands to the ASD via RS485 4-wire.
4 — Communication Option Board
Use this setting if using the optional Communication Board for command control.
Frequency Control
Selections
The following is a listing with descriptions of the
Frequency Mode (F004) selections (Program 
Fundamental  Standard Mode Selection 
Frequency Mode 1).
Settings:
1 — VI/II (V/I)
Used when a 0 to 10-volt DC analog input or a 0 – 20 mA DC current input is used as the speed
control input. Only one input signal type may be used at a time. Set SW301 to the desired signal
type.
2 — RR
Used for a 0 to 10-volt DC analog input signal.
3 — RX
Used for a -10 to +10-volt DC analog input signal.
4 — Not Used
Unused.
5 — EOI Keypad
Used for EOI frequency control.
6 — RS485
Used to transfer speed commands to the ASD via RS485 4-wire.
G9 ASD Installation and Operation Manual
Standard Mode Selection
(F003) Command Mode
Selection
(Default)
Terminal Block
Standard Mode Selection
(F004) Frequency Mode 1
(Default)
RR
(Default)
01:06
02:06
39