F959
Analog Input Function Target 11
Program My Function My Function Analog
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Analog Input Function
Target 11 terminal.
The function selected at
F961
may be adjusted using the input analog control
signal selected here.
Settings:
0 — Disabled (None)
1 — VI/II (V/I)
2 — RR
3 — RX
4 — Optional RX2+, RX2-
5 — Optional V/I
Analog Function Assigned Object 11
Program My Function My Function Analog
This parameter plays a role in the setup of the My Function feature by
selecting the functionality to which the adjustment of
Settings:
0 — Disabled (None)
1 — Acceleration Rate
2 — Upper-Limit Frequency
3 — Acceleration Multiplication Factor
4 — Deceleration Multiplication Factor
5 — Manual Torque Boost
6 — Over-Current Stall (F601)
7 — Thermal Protection (F600)
8 — Speed Loop Proportional Gain (F460)
9 — Drooping Gain (F320)
10 — PID Proportional Gain (F362)
See the My Function Instruction Manual (P/N E6581335) for a complete
description of the setup requirements and operational information of the Analog
Function Assigned Object parameter.
Analog Input Function Target 21
Program My Function My Function Analog
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Analog Input Function
Target 21 terminal.
The function selected at
F964
may be adjusted using the input analog control
signal selected here.
Settings:
0 — Disabled (None)
1 — VI/II (V/I)
2 — RR
3 — RX
4 — Optional RX2+, RX2-
5 — Optional V/I
226
Direct Access Number — F959
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Direct Access Number — F961
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
F959
is applied.
Direct Access Number — F962
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
G9 ASD Installation and Operation Manual