F669
Selection of OUT Terminal
Program Terminal Analog Output Terminals
This parameter is used to enable the OUT1 and OUT2 output terminals, or the
FP output terminal by selecting Logic Output or Pulse Train Output,
respectively.
Note:
The Logic output and the Pulse Train output may not be used
simultaneously.
If Logic Output is selected the OUT1 and OUT2 (O1A/O1B and O2A/O2B)
output contacts of the Terminal Board are enabled to function as described in
parameter F130.
The OUT1 and OUT2 terminals may be used simultaneously and they may be
assigned different functions.
If Pulse Train Output is selected the FP output terminal of the Terminal
Board is enabled to function as configured in
Settings:
0 — Logic Output
1 — Pulse Train Output
AM Output Terminal Function
AM
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the AM analog output
terminal. The AM analog output terminal produces an output current that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in
Note:
To read current at this terminal connect a 100 – 500
from the AM (+) terminal through the series Ammeter to the CC
(-) terminal.
AM Terminal Setup Parameters
F670
— Set AM Function
F671
— Calibrate AM Terminal
F685
— Output Response Polarity Selection
F686
— Set Zero Level
AM Output Terminal Adjustment
Program Terminal Analog Output Terminals
This parameter is used to calibrate the AM analog output.
To calibrate the AM analog output, connect an ammeter as described at
parameter F670.
With the drive is running at a known value (e.g., output frequency), adjust this
parameter until the associated function of parameter
DC level output at the AM output terminal.
See
F670
for more information on this setting.
192
efesotomasyon.com -Toshiba inverter,drive,servo,plc
F676
and F677.
F670
Direct Access Number — F669
Parameter Type — Selection List
Factory Default — Pulse Train Output
Changeable During Run — No
Direct Access Number — F670
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes
Table 6 on pg.
237.
resistor
Direct Access Number — F671
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
produces the desired
G9 ASD Installation and Operation Manual