Toshiba G9 Installation And Operation Manual page 130

Asd
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
F234
PG Input Point 1 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the PG input terminal of the
option board when a shaft-mounted encoder is used as the control input while
operating in the Speed Control mode.
Note:
See PG Option Board Instruction Manual P/N 58687 for more
information.
PG Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the PG input terminal:
• Program Fundamental Standard Mode Selection Frequency Mode
1 Pulse Input (option).
• Program Fundamental Standard Mode Selection Command Mode
Selection (any setting).
• Provide a Run command (F and/or R).
Speed Control
Perform the following setup to allow the system to perform Speed control from
the PG input terminals:
• Set PG Point 1 Frequency (F235).
• Set the PG input value (F234) that represents PG Point 1 Frequency.
• Set PG Point 2 Frequency (F237).
• Set the PG input value (F236) that represents PG Point 2 Frequency.
Once set, as the PG input pulse count rate changes, the output frequency of the
drive will vary in accordance with the above settings.
This parameter sets the PG input pulse count that represents Reference
Setpoint 1 (frequency). The range of values for this parameter is 0% to 100%
of the PG input pulse count range.
Note:
Further application-specific PG settings may be performed from
the following path: Program Feedback PG Settings
PG Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the speed of the PG input terminals when the PG
terminal is used as the control input.
This parameter sets PG Point 1 Frequency and is the frequency that is
associated with the setting of PG Point 1 Setting.
See PG Point 1 Setting (F234) for further information on this setting.
122
F235
Direct Access Number — F234
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0
Maximum — 100.0
Units — %
Frequency Settings
Direct Access Number — F235
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz