Toshiba G9 Installation And Operation Manual page 173

Asd
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
F502
Acc/Dec Pattern 1
Program Special  Accel/Decel 1 – 4 Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the 1 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
The figures below provide a profile of the available accel/decel patterns.
Linear acceleration and deceleration is the
default pattern and is used on most
applications.
S-pattern 1 is used for applications
that require quick acceleration and
deceleration. This setting is also
popular for applications that require
shock absorption at the start of
acceleration or deceleration.
S-pattern 2 decreases the rate of change
above the base frequency for acceleration
and deceleration.
G9 ASD Installation and Operation Manual
F502
Direct Access Number — F502
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
165

Advertisement

Table of Contents
loading

Table of Contents