Toshiba G9 Installation And Operation Manual page 214

Asd
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
F813
Point 2 Setting
Program Communications Communication Reference Adjust
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See
F811
for more information on this setting.
This parameter sets the Communications Reference input value that represents
Communications Reference Speed Setpoint 2 (frequency). This value is
entered as 0 to 100% of the Communications Reference input value range.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Point 2 Frequency
Program Communications Communication Reference Adjust
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See
F811
for more information on this setting.
This parameter sets the Communications Reference Speed Setpoint 2.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
RS485 Baud Rate
Program Communications Communication Settings
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
RS485 Send Wait Time
Program Communications Communication Settings
This parameter sets the RS485 response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
206
F825
Direct Access Number — F813
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Direct Access Number — F814
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F820
Parameter Type — Selection List
Factory Default — 19200
Changeable During Run — Yes
Direct Access Number — F825
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
G9 ASD Installation and Operation Manual