F622
Abnormal Speed Detection Time
Program Protection Abnormal Speed Settings
This parameter sets the time that an overspeed condition must exist to cause a
trip.
This parameter functions in conjunction with the settings of
Over-Speed Detection Frequency Upper Band
Program Protection Abnormal Speed Settings
This parameter sets the upper level of the Base Frequency range that, once
exceeded, will cause an Over-Speed Detected alert.
This parameter functions in conjunction with the settings of
Over-Speed Detection Frequency Lower Band
Program Protection Abnormal Speed Settings
This parameter sets the lower level of the Base Frequency range that, once the
output speed falls below this setting, will cause a Speed Drop Detected alert.
This parameter functions in conjunction with the settings of
Over-Voltage Limit Operation Level
Program Protection Stall
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Over-Voltage Stall. An Over-Voltage Stall increases the output
frequency of the drive during deceleration for a specified time in an attempt to
prevent an Over-Voltage Trip.
If the over-voltage condition persists for over 4 mS, an Over-Voltage Trip will
be incurred.
This parameter is enabled at F305.
Note:
This parameter setting may increase deceleration times.
Under-Voltage Trip
Program Protection Under-Voltage/Ridethrough
This parameter Enables/Disables the Under-Voltage Trip function.
With this parameter Enabled, the ASD will trip if the under-voltage condition
persists for a time greater than the
A user-selected contact may be actuated if so configured.
If Disabled the ASD will stop and not trip; the FL contact is not activated.
Settings:
0 — Disabled
1 — Enabled
G9 ASD Installation and Operation Manual
F623
and F624.
F622
and F624.
F622
and F623.
F628
setting.
F627
Direct Access Number — F622
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.00
Units — Seconds
Direct Access Number — F623
Parameter Type — Numerical
Factory Default — 0.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.0 (Disabled)
Maximum — 30.00
Units — Hz
Direct Access Number — F624
Parameter Type — Numerical
Factory Default — 0.00 (Disabled)
Changeable During Run — Yes
Minimum — 0.00 (Disabled)
Maximum — 30.00
Units — Hz
Direct Access Number — F626
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 100
Maximum — 150
Units — %
Direct Access Number — F627
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
187