Toshiba G9 Installation And Operation Manual page 209

Asd
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
F740
Trace Selection
Program Utilities Trace
In conjunction with parameter
F741
and store 4 ASD output waveform data points. The data may be read and stored
as a function of a trip (At Trip) or it may be initiated by the activation of a
discrete terminal activation (At Trigger).
Set a discrete input terminal to Trace Back Trigger Signal and activate the
terminal to initiate the At Trigger read/store function.
Table 10 on pg. 241
lists the items that may be selected for the data read/store
function along with the associated communication number for each selection.
The duration of the read/store cycle for the selected items is set at parameter
F741.
To acquire and store the data a communications device and a PC are required.
The G9 ASD supports the following communications protocols: RS485
(MODBUS-RTU) Toshiba Protocol, USB Toshiba Protocol, CC-Link,
ProfiBus, and DeviceNet (Refer to the manual of each protocol type for more
information).
Trace data may be viewed graphically via Program  Utilities  View Trace
Data.
Settings:
0 — None (Disabled)
1 — At Trip
2 — At Trigger
Trace Cycle
Program Utilities Trace
This parameter sets the record time for the Trace Data events selected at
– F745.
See
F740
for more information on this parameter setting.
Settings:
0 — 4 mS
1 — 20 mS
2 — 100 mS
3 — 1 Second
4 — 10 Seconds
Trace Data 1
Program Utilities Trace Data 1
This parameter is used to select the Trace Data 1 item from
to be read and stored in accordance with the setup of parameters
F741.
See
F740
for more information on this parameter setting.
Trace Data 2
Program Utilities Trace Data 2
This parameter is used to select the Trace Data 2 item from
to be read and stored in accordance with the setup of parameters
F741.
See
F740
for more information on this parameter setting.
G9 ASD Installation and Operation Manual
– F745, this parameter is used to monitor
Table 9 on pg. 240
F740
and
Table 9 on pg. 240
F740
and
Direct Access Number — F740
Parameter Type — Selection List
Factory Default — At Trip
Changeable During Run — Yes
Direct Access Number — F741
Parameter Type — Selection List
Factory Default — 100 mS
F742
Changeable During Run — Yes
Direct Access Number — F742
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Direct Access Number — F743
Parameter Type — Selection List
Factory Default — Freq. Reference
Changeable During Run — Yes
F743
201