Direct Access Parameter Information

The ASD has the ability to allow the user direct access to the motor-control functions. There are two ways
in which the motor-control parameters may be accessed for modification: Program Applicable Menu
Path or Program  Direct Access  Applicable Parameter Number.Both methods access the parameter
via the Program mode. Once accessed, the parameter may be viewed or changed.
The Program mode allows the user to develop an application-specific motor-control profile. Motor-
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers are listed and described below.
Note: Parameter selections are preceded by the number used to select an item if using
communications to write to a parameter location in memory (i.e., F000  0-Manual, 1- No
Trip on Acc/Dec, 2-No trip on Acc Only, etc.).
Note: The setup procedures included within this section may require a Reset before performing the
procedure. Application-specific settings may then be performed. The pre-Reset conditions
may be saved (see F007).
Note: Communications setting changes will require that the power be removed and then re-applied
for the changes to take affect.

Direct Access Parameters/Numbers

Automatic Acceleration/Deceleration
Program  Fundamental Accel/Decel 1 Settings
This parameter is used to enable automatic acceleration and deceleration rates
in accordance with the applied load.
The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed values for Acceleration Time 1 (F009) and Deceleration
Time 1 (F010).
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC Only
Note:
The motor and the load must be connected prior to selecting
Automatic Acceleration/Deceleration.
Automatic Torque Boost
Program  Fundamental Motor Set 1
This parameter allows the ASD to adjust the output torque in accordance with
the applied load automatically. When enabled Autotuning is performed — the
motor should be connected before performing an Autotune.
Settings:
0 — Disabled
1 — Automatic Torque Boost + Autotuning
2 — Sensorless Vector Control + Autotuning
76
F001
Direct Access Number — F000
Parameter Type — Selection List
Factory Default — Manual
Changeable During Run — No
Direct Access Number — F001
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
G9 ASD Installation and Operation Manual