F190
V/f 5-Point Setting Frequency 1
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 1 setting establishes the frequency that is
to be associated with the voltage setting of
1).
The V/f 5-Point settings define a volts per hertz relationship for the startup
output of the ASD.
To enable this function, set the V/f Pattern (F015) selection to the V/f 5-Point
Curve setting.
V/f Curves may be useful in starting high inertia loads such as rotary drum
vacuum filters.
G9 ASD Installation and Operation Manual
F191
(V/f 5-Point Setting Voltage
F190
Direct Access Number — F190
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz