Toshiba G9 Installation And Operation Manual page 31

Asd
Table of Contents

Advertisement

SU+
P24
PP
O1A/B
O2A/B
G9 ASD Installation and Operation Manual
efesotomasyon.com -Toshiba inverter,drive,servo,plc
RX — The default function assigned to this terminal is the Torque Command setting. The RX
terminal accepts a ±10 VDC input signal that is used to carry out the function assigned to this terminal.
This input terminal may be programmed to raise or lower the speed or torque of the motor via an
amplitude setting. This terminal may also be used to regulate the speed or torque of a motor by setting a
limit. The gain and bias of this terminal may be adjusted for application-specific suitability (see
F221). See
Figure 20 on pg. 26
CCA.
V/I — The V/I terminal has the dual function of being able to receive an input voltage or current. The
function as a voltage input to receive a 0 – 10 VDC input signal. The function as a current input is to
receive a 0 – 20 mA input signal. Using either input type, the function is to control the 0.0 – Maximum
Frequency output or the 0.0 to 250% torque output of the ASD. This is an isolated input terminal. This
terminal may be programmed to control the speed or torque of the motor and cannot process both input
types simultaneously. SW301 must be set to V or I to receive a voltage or current, respectively (see
Figure 9 on pg.
24). Terminal scaling is accomplished via
terminal may be adjusted for application-specific suitability (see
SU+ — Externally supplied +24 VDC ±10% at 1.1 A (minimum) backup control power. This terminal
references CC.
P24 — +24 VDC at 200 mA power supply for customer use. This terminal references CCA.
PP — The function of output PP is to provide a 10 VDC/10 mADC output that may be divided using a
potentiometer. The tapped voltage is applied to the RR input to provide manual control of the RR
programmed function. This terminal references CCA.
O1A/B (OUT1A/B) — The default function assigned to this terminal is Output Low Speed. This
output may be programmed to provide an indication (open or closed) that any one of the functions listed
in
Table 8 on pg. 239
has occurred or is active. This function may be used to signal external equipment
or to activate the brake (see F130). The OUT1 terminal is rated at 2 A/120 VAC and 
2 A/30 VDC.
O2A/B (OUT2A/B) — The default function assigned to this terminal is ACC/DEC Complete. This
output may be programmed to provide an indication (open or closed) that any one of the functions listed
in
Table 8 on pg. 239
has occurred or is active. This function may be used to signal external equipment
or to activate the brake (see F131). The OUT2 terminal is rated at 2 A/120 VAC and 
2 A/30 VDC.
FP — The default function of this output terminal is to output a series of pulses at a rate that is a
function of the output frequency of the ASD (50 mA max. at 1.0 kHz to 43.3 kHz). As the output
frequency of the ASD goes up so does the FP output pulse rate. This terminal may be programmed to
provide an output pulse rate that is proportional to the magnitude of the user-selected item from
on pg.
237. For further information on this terminal see
AM — This output terminal produces an output current that is proportional to the output frequency of
the ASD or of the magnitude of the function assigned to this terminal. The available assignments for
this output terminal are listed in
on pg.
192.
FM — This output terminal produces an output current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the function assigned to this terminal. The available
assignments for this output terminal are listed in
terminal see
F005 on pg.
78. The Voltage/Current output selection is performed at F681.
for an electrical depiction of the RX terminal. This terminal references
F201
F676 on pg.
Table 6 on pg.
237. For further information on this terminal see
Table 6 on pg.
– F206. The gain and bias of this
F470
and F471).
194.