Toshiba G9 Installation And Operation Manual page 125

Asd
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
F223
RX2 (AI1) Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets RX2 (AI1) Input Point 1 Frequency and is the frequency
that is associated with the setting of RX2 (AI1) Input Point 1 Setting when
operating in the Speed Control mode.
See RX2 (AI1) Input Point 1 Setting (F222) for more information on this
setting.
RX2 (AI1) Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.
This parameter sets the RX2 (AI1) input level that is associated with RX2
(AI1) Input Point 2 Frequency when operating in the Speed control mode or
is associated with the RX2 (AI1) Input Point 2 Rate when operating in the
Torque Control mode.
This value is entered as -100% to +100% of the RX2 (AI1) input signal range.
See RX2 (AI1) Input Point 1 Setting (F222) for more information on this
setting when used for Speed control.
See RX2 (AI1) Input Point 1 Rate (F226) for more information on this setting
when used for Torque Control.
RX2 (AI1) Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets RX2 (AI1) Input Point 2 Frequency and is the frequency
that is associated with the setting of RX2 (AI1) Input Point 2 Setting when
operating in the Speed Control mode.
See RX2 (AI1) Input Point 1 Setting (F226) for more information on this
setting.
G9 ASD Installation and Operation Manual
F225
Direct Access Number — F223
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
117

Advertisement

Table of Contents
loading

Table of Contents