F138
Output Terminal 9 (R2) Function
Program Terminal Output Terminals
This parameter is used to set the functionality of the R2 discrete output
terminal.
In addition, this output terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable R2 terminal to any one of
the user-selectable functions listed in
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for
more information on the function of this terminal.
Input Terminal 1 (F) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 2 (R) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the drive to any change in the R terminal
input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 3 (ST) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the drive to any change in the ST
terminal input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
G9 ASD Installation and Operation Manual
Table 8 on pg.
239.
F142
Direct Access Number — F138
Parameter Type — Selection List
Factory Default — Always Off
Changeable During Run — No
Direct Access Number — F140
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F141
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F142
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS