F802
ASD Number
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Communications Time Out Time
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
RS485 2- and 4-Wire Communications Time-Out Action
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the drive.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
(Settings Are For 2-Wire/4-Wire)
0 — No Action/No Action
1 — Alarm/No Action
2 — Trip/No Action
3 — No Action/Alarm
4 — Alarm/Alarm
5 — Trip/Alarm
6 — No Action/Trip
7 — Alarm/Trip
8 — Trip/Trip
G9 ASD Installation and Operation Manual
F804
Direct Access Number — F802
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 247
Direct Access Number — F803
Parameter Type — Numerical
Factory Default — 0 (Off)
Changeable During Run — Yes
Minimum — 0 (Off)
Maximum — 100
Units — Seconds
Direct Access Number — F804
Parameter Type — Selection List
Factory Default — Trip/Trip
Changeable During Run — Yes
203