Electrical Installation Specifications; General Requirements; Requirements For Precomissioning - ABB Terra HP Generation 4 CE Ionity Installation Manual

Table of Contents

Advertisement

Technical data
12.6

Electrical installation specifications

12.6.1

General requirements

Parameter
Circuit breaker
Surge protection device
Residual-current device
Power consumption of the power cabi-
net
Power consumption of the charge post
Earthing system
Input AC power connection
Input voltage range
Nominal input current
Maximum input current
Cores
Phases cross section range (recom-
mended )
PE cross section range (recommended )
Cable lug maximum width
Power factor at full load
Efficiency
THD
Reactive power (capacitive)
12.6.2

Requirements for precomissioning

Parameter
Circuit breaker
Surge protection device
Power consumption
Earthing system
Input AC power connection
70
Specification
Use a circuit breaker with the option for
an under voltage release device.
Type 2
In the range of 30 mA up to 300 mA
In standby status: ≤ 86.7 W
In standby status: ≤ 70 W
With the LEDs on: ≤ 145 W
TN-C
TN-S
TN-CS
TT
400/230 VAC 3W + PE
400 V AC +/- 10 % (50 Hz or 60 Hz)
550 A at 400 V AC
610 A at 360 V AC
According to IEC 60446, aluminum - cop-
per
2
2 x 120 mm
to 180 mm
2
or 1 x 240 mm
to 300 mm
2
2
120 mm
to 180 mm
40 mm, M12
> 0.99
≥ 92 % at ≥ 20 % load
≥ 95 % at full load
< 6 % for > 90 kW output power
≥ 9 % at full load
Specification
25 A type C
Type 2
In standby status: ≤ 1800 W
TN-C
TN-S
TN-CS
TT
230 V AC 1P + PE
6AGA000032-0115-EN | 004
2
per phase
2
per phase