8.4

Connect the AC auxiliary power cable

Preliminary requirements
Procedure
1. Strip the insulation from the ends
of the wires (A) to (D). For the
specification, refer to section 11.2.
2. Crimp ferrules onto the end of the
wires.
3. Loosen the screws of the terminals (E)
to (H) of the terminal block X-10.
4. Connect these wires:
5. Tighten the screws to the correct torque. For the specification, refer to section
12.13.
8.5
Connect the interlock and DC guard cable
Preliminary requirements
6AGA000032-0115-EN | 004
Wire cutter
Wire stripper pliers
Torque screwdriver, cross
Crimp pliers
AC auxiliary power cable
Ferrules
Note: The AC auxiliary power cable provides the control power to the
charge post.
PE wire (A), green/yellow, to the
terminal X10-1 (E)
L1 wire (B), brown, to the terminal
X10-2 (F)
L2 wire (C), black, to the terminal
X10-3 (G)
L3 wire (D), gray, to the terminal X10-4 (H)
Note: For a detailed overview of all electrical connections, refer to
section 12.19.
Torque screwdriver, cross
Interlock and DC guard
cable. Refer to section
12.18.5.
Ferrules
Electrical installation of the charge post
H
G
F
E
D
C
B
A
53