Changes Of The State Machine - KEB COMBIVERT F6 Programming Manual

Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

State machine
disable operation active
State disable operation active is reached when:
Power Off:
State Power Off is reached when:
i

Changes of the state machine

All possible changes between the different states of the state machine can be
found in the picture in chapter4.1 State
Setting of bit 3 Enable Operation in the
Operation function.
Setting of bit 2 no Qickstop can deactivate Quickstop Reaction Active.
Disable Operation Active can be interrupted by Shutdown Operation Active.
Quickstop Reaction Activecan not be interrupted by Shut Down Active, inde-
pendent of the selected response to the Switch On Bit.
Fault Reaction Active has the highest priority and can interrupt Shutdown Oper-
ation Active, Disable Operation Active and Quickstop Reaction Active .
Exception:
Removal of bit 1 enable voltage always leads to an immediate shutdown of the
modulation.
© 2022 KEB Automation KG
Bit Enable Operation is reset in state Operation enabled.
A mains power failure is detected and the Power Off function has been ac-
tivated in the cu parameters (see chapter 4.4.22).
➢ The states "shutdown operation active", "disable operation active" and
"fault reaction active" are only carried out with the appropriate setting of
the state machine. The behavior in these states is defined in co32.
Fault Reaction Active is interrupted by Shut Down, if shutdown mode is
set as direct shutdown
(shutdown option code
or co32 state machine properties
machine
.
controlword
can deactivate the Disable
= „0: disable drive function"
= „0: direct").
Mode
shutdown mode
23