Protection functions

Overspeed (ERROR overspeed / ERROR overspeed (EMF))

Index
Id-Text
Name
0x2A1B
pn26
overspeed level
0x2A1C
pn27
E.overspeed stop mode
0x2A46
pn70
overspeed factor (EMF)
E. overspeed EMF) st.
0x2A47
pn71
mode
0x2A48
pn72
overspeed level (EMF)
There are 2 functions for overspeed protection
NOTICE
© 2022 KEB Automation KG
Note
Tripping level ERROR overspeed in % rated
speed
Error reaction (=> see Chapter 4.3.1 Errors)
Tripping level ERROR overspeed (EMF)
Error reaction (=> see Chapter 4.3.1 Errors)
Tripping level ERROR overspeed (EMF) in rpm
An application-specific speed limit can be set with pn26.
It is calculated from the value of the EMF at which speed the regenerative
voltage of the synchronous machine reaches a value which damage the
capacitors in the inverter DC link. The safety difference to this limit is pre-
set with
pn70 overspeed factor
the error is triggered at 90% of the max. theoretically permissible speed
value. The level when the error is triggered is displayed in
level
(EMF).
������ ��
����70
����72 =
∗ 1000 ∗ ����
�� 14
100%
The response to the error is defined with
mode.
➢ These errors are only triggered when the modulation is switched
on.
(pn26
/
pn27
and pn70...pn72).
(EMF). A value of 90% for
pn71 E. overspeed (EMF) st.
pn70
means,
pn72 overspeed
83