Protection functions
The reaction to the warning is freely adjustable. All setting options for configurable
errors are available.
The default setting is "Warning". That means: upon reaching the pre-warning tem-
perature, bit 2 is set in
mask also bit 7 in the status word.
pn06
defines how the reference level for generating the overtemperature warning
is determined:
pn06
temperature warning setting mode
Value
Name
0
absolute value
1
relative to error level
T [°C]
T (OH)
pn07
Warning
off
Error
T(OH):
pn07:
21
1

Figure 10: Overtemperature heatsink (OH)

© 2022 KEB Automation KG
ru02 warning bits
Function
ru25[1] heatsink temperature
ru25[3] heatsink temperature 3
level.
If one of the heatsink temperatures is higher than the comparison value,
the warning becomes active. If all heatsink temperatures are lower than
the comparison value minus the hysteresis (5 °C), the warning is reset.
pn07 OH warning level
ping threshold whose undershooting shall trigger the warning.
If one of the heatsink temperatures is closer to its associated shutdown
threshold than pn07, the warning becomes active. The warning will be
reset if all heatsink temperatures are outside the range of
teresis (5 °C).
on
off
No exception
device-dependent switch-off temperature
adjustable OH warning level
1fghfh
and with respective setting of the warning
1,
ru25[2] heatsink temperature 2
are compared with
defines the distance to the overtemperature trip-
on
off
E.OH
reset E.OH
0x2A06
and
pn07 OH warning
pn07
plus hys-
t
63