Fan Control S6-A / S6-K; Terminals Short Circuit Protection; Control Type K; Control Type A - KEB COMBIVERT F6 Programming Manual

Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

Terminals short circuit protection

Fan control S6-A / S6-K

The S6 servo controller has only one fan, which is controlled by the interior (ID) or
heat sink (HS) temperature.
The fan is activated in the default setting for unit sizes 9, 10 or 11, if the interior
temperature or the heatsink temperature exceeds 50°C.
This threshold is dependent on the power unit and can vary for other sizes or spe-
cial devices.
The switch-off threshold is 5°C below the switch-on threshold and the minimum
switch-on time is 5s.
The switch-on temperature can be changed by parameters
de116
cooling fan HS level
de117
cooling fan ID level
Value
Meaning
-1: on
Fan is always on
0: LT Value
Fan is activated with default setting
Activation threshold in °C, is limited upwards depending on the power unit.
0,1...50,0
(For unit size 9, 10 or 11 the upper limit is equal to the default setting = 50 °C)
4.7
Terminals short circuit protection

Control type K

The digital outputs Out 1...Out 4 on the terminal blocks X2A and X2B, as well as
the voltage outputs 24V OUT and the 24V encoder supply are short-circuit pro-
tected.
However, the current is not limited to the maximum permissible value (=> installa-
tion manual), but it is a thermal protection.
Thus the inverter is protected against destruction, but the 24V supply can failure
due to overload.
If the supply voltage does not failure, the inverter changes to the following errors:
Short circuit of a digital output
Short circuit of a 24V voltage output
Short circuit of the 24V encoder supply

Control type A

The digital outputs Out 1 and Out 2 on the terminal block X2A, as well as the volt-
age outputs 24V OUT and the 24V encoder supply are short circuit protected.
However, the current is not limited to the maximum permissible value (=> installa-
tion manual), but it is a thermal protection.
124
de116
/ de117.
0x2074
0x2075
100 "ERROR overcurrent out1"
101 "ERROR overcurrent out2"
102 "ERROR overcurrent out3"
103 "ERROR overcurrent out4"
106 "ERROR overcurrent 24V"
105 "ERROR overcurrent en-
coder"