Affect The Behaviour Of The State Machine - KEB COMBIVERT F6 Programming Manual

Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

State machine
st12
state machine display
Value
State
Mod off pause active
12
Power Off
13
protection time active
14
protection time end
15
endless protection time
16
suppressed error
17
The detailed description of the single states of the state machine and the changes
can be found in chapter 4.1 State
st13
state and error display
Bit
Name
0...7
error display
8...15
state display
This parameter is used to indicate the reason for the triggering of a stop function
(Fault-Reaction / ShutDown / Quickstop / DisableOperation), even if the internal
error state is no longer present during the ramp.
The display of the error is not reset via a reset, but only by the request of a new
state machine change via the internal controlword.

Affect the behaviour of the state machine

The behaviour of the state machine can be affected via parameter
chine
properties.
Index
Id-Text
Name
0x2520
co32
state machine properties
28
Note
Minimum switch-off time of the modulation not yet expired
Power Off function active
A protection time (minimum switch-off time after error) is active
For more detailed information see chapter (4.4.23 Minimum switch-
off times.
An applied error leads to modulation shutdown, but it is not dis-
played as an error in
machine
Note
Value of ru01 (see 4.3.1 Errors)
Value of st12 * 256
ru01
and the state parameters.
.
Function
KEB spec. Object
0x210C
0x210D
co32 state ma-
© 2022 KEB Automation KG