External Error / Warning Triggering; Safety Stop From Safety Module - KEB COMBIVERT F6 Programming Manual

Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

Protection functions

External error / warning triggering

Index
Id-Text
Name
0x2A1D
pn29
prg. error stop mode
0x2A1E
pn30
prg. error source
Errors or warnings can also be triggered by external events. Different sources can
be selected via pn30.
The meaning of the single bits in
pn30
Bit
Value
Name
0
1
I1
1
2
I2
2
4
I3
3
8
I4
4
16
I5
5
32
I6
6
64
I7
7
128
I8
8
256
IA
9
512
IB
10
1024
IC
11
2048
ID
12...1
5

Safety Stop from safety module

Index
Id-Text
Name
safety stopping func-
0x2A50
pn80
tion
© 2022 KEB Automation KG
Function
Error reaction (=> see Chapter 4.3.1 Errors)
Selection of the inputs or events which trigger the error
pn30 prg. error source
prg. error source
Input I1 triggers an error
Input I2 triggers an error
Input I3 triggers an error
Input I4 triggers an error
Input I5 triggers an error
Input I6 triggers an error
Input I7 triggers an error
Input I8 triggers an error
Input IA triggers an error
Input IB triggers an error
Input IC triggers an error
Input ID triggers an error
Reserved
Function
Error reaction (=> see Chapter 4.3.1 Errors)
On devices with safety module type 3 or higher, the SS1 or
SS2 function can directly execute the reaction set in pn80.
See also the instruction manual of the safety module.
is defined as follows:
0x2A1E
Function
77