Electrical connection

2.3
Electrical connection
DANGER
For a trouble-free and safe operation, please pay attention to the following instruc-
tions:
The electrical installation shall be carried out in accordance with the relevant
requirements.
Cable cross-sections and fuses must be dimensioned according to the design of
the machine manufacturer. Specified minimum / maximum values may not be
fallen below /exceeded.
With existing or newly wired circuits the person installing the units or machines
must ensure the EN requirements are met.
For drive controllers that are not isolated from the supply circuit (in accordance
with
measures (e.g. double insulation or shielded, earthed and insulated).
When using components without isolated inputs/outputs, it is necessary that
equipotential bonding exists between the components to be connected (e.g. by
the equipotential line). Disregard can cause destruction of the components by
equalizing currents.
2.4

Start-up and operation

The drive controller must not be started until it is determined that the installation
complies with the machine directive; Account is to be taken of
WARNING
16
Electrical voltage at terminals and in the device!
Danger to life due to electric shock!
➢ For any work on the device switch off the supply voltage and secure it
against switching on.
➢ Wait until the drive has stopped in order that no regenerative energy
can be generated.
➢ Await capacitor discharge time (5 minutes) if necessary, measure DC
voltage at the terminals.
➢ Never bridge upstream protective devices (also not for test purposes)
EN
61800-5-1) all control lines must be included in other protective
Software protection and programming!
Danger due to unintentional behaviour of the drive!
➢ Check especially during initial start-up or replacement of the drive
controller if the parameterization is compatible to the application.
➢ Securing a unit solely with software-supported functions is not suffi-
cient. It is imperative to install external protective measures (e.g. limit
switch) that are independent of the drive controller.
➢ Secure motors against automatic restart.
EN
60204-1.