Figure 4.3-23 LN editing screen for SBO mode (for example)
Defining DIR mode
Figure 4.3-24 exemplifies the settings in LN "GGIO701" when the DIR mode is required for
the SOFTSW1 function. In the DIR mode, the following three items should be selected using
GR-TIEMS:
Figure 4.3-24 LN editing screen for DIR mode (for example)
Mapping output data
(ii)
The user should group the SOFTSW1 (S4301) signals with regard to GOOSE and REPORT;
the user should map them for IEC 61850 communication using GR-TIEMS.
SBOw
✓
Oper
✓
Cancel
✓
Origin
✓
stSeld
✓
sboClass (choice "operate-once")
✓
ctlmodel (choice "SBOes or SBOns" )
✓
Oper
✓
origin
✓
ctlmodel (choice "DOes or DOns" )
✓
- 756 -
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)