Toshiba GR200 Series Instruction Manual page 740

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting for "Select command Closing"
For example, the point "DPSY01_OSL_BO_FLG" is connected to the BO1 circuit for the issuing
of the command; the user can connect point "BO1-RB" with the contact health check function
using the setting [DPSY01-OSLBORD]. Do not key the point "DPSY01_OSL_BO_FLG".
Figure 4.2-45 Example connection of "Select command Closing" for the health check feature
Setting the "Select command Open"
Similar to "select command Closing", the point "DPSY01_FSL_BO_FLG" is connected with the
BO2 circuit; the user is required to key point "BO2-RB" for the setting [DPSY01-FSLBORD].
Do not key the point "DPSY01_FSL_BO_FLG".
Figure 4.2-46 Example connection of "Select command Open" for the health check feature
Setting for "Operate command Closing"
Similarly, the point "BO3-RB" must be applied for the setting [DPSY01-OEXBORD].
Selection logic in
DPSY01
"
"
DPSY01_OSL_BO_FLG
(511001 8602011DC6)
BO1 circuit at
IO#1
"
"
BO1-RB
(200B01_8002001113)
Signal connected by
setting [DPSY01-OSLBORD]
Connection made by the user
Selection logic in
DPSY01
"
"
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
BO1 circuit at
IO#1
"
"
BO2-RB
(200B01_8102001113)
Signal connected by
setting [DPSY01-FSLBORD]
Connection made by the user
Contact health check
logic in DPSY01
Result of contact
health check
&
Contact health check
logic in DPSY01
Result of contact
health check
&
- 717 -
6F2S1914 (0.49)