ABB ProKiln GAC400 Operating Instruction page 32

Probe gas sampling system
Table of Contents

Advertisement

32
ProKiln GAC400 PROBE GAS SAMPLING SYSTEM | OI/GAC400-EN REV. A
... 3 Design and function
... Default operation parameter settings
Parameter input M1 Motor Control menu
Figure 25: M1 Motor Control menu
Parameter input
Function
Torque limit
Protective limit for motor and gear
M1 Run
Motor run
M1 Switch On
Operation allowed
Stop Coast
Stop at retracted position
Stop Ramp
Run direct speed control
M1 Break release
Release the brake to move buggy
Horn On
The horn will sound during movement
of probe
Failure sec.
Maximum time allowed for the probe
to move
Parameter input - PID H1 Probe heater Setup menu
Figure 26: PID H1 Probe heater Setup menu
Parameter input
Function
Setp.
Temperature set-point of sample tube
inside of the probe
Reset
Reset to factory setting
On/Off
Power control for heater
Parameter input PID H2 Heated hose setup menu
Figure 27: PID H2 Heated hose setup menu
Parameter input
Default value
65%
Setp.
Status of motor
The motor can run
Reset
On
On/Off
On
Parameter input PID H3 Heated valve setup menu
Off
On
60 sec.
Figure 28: PID H3 Heated valve setup menu
Parameter input
Setp.
Reset
On/Off
Default value
180 °C
On
Function
Temperature set-point of heated hose
inside of the retractor
Reset to factory settings
Power control for heater
Function
Temperature set-poin of heated shut-
off valve (if available)
Reset to factory settings
Power control for heater
Default value
180 °C
On
Default value
180 °C
On