Cr750 Controller - Mitsubishi MELFA RH-3FH-D Series Special Specifications Manual

Table of Contents

Advertisement

3.7.2 Special stop input (SKIP)
The skip is the input signal to stop the robot. The pin 9, 34 of the CNUSR2 connector shown in
(CR750) or
Fig. 3-17
Table 3-4 : Special stop input electric specification
Item
Type
No. of input point
Insulation method
Rated input voltage
Rated input current
Working voltage range
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response
OFF → ON
time
ON → OFF
Common method
External wire connection method

(1) CR750 controller

* Connects with CNUSR2 connector
with soldering.
Refer to
Page 86 "Fig. 3-12: Method
of wiring for external emergency stop
connection (CR750
Note) In the customer's system, do not ground the + side of 24V power supply prepared by customer for con -
nect to the controller. (related with emergency stop and parallel input/output) If it connects with the con -
troller under the condition that the + side is grounded, it will lead to failure of controller.
Fig.3-16 : Connection of the special-stop-input (CR750)
(CR751).
Specifications
DC input
1
Photo-coupler insulation
DC24V
Approx. 11mA
DC 21.6 ~ 26.4V
(Ripple rate within 5%)
DC 8V or more / 2mA or more
DC 4V or less / 1mA or less
Approx. 2.2 k Ω
1ms or less
1ms or less
1 point per common
Connector
Within 30cm
30cm以内
(CNUSR2))".
Internal circuit
330
2.2k
CNUSR2 connector
CNUSR2
Ferrite core
フェライトコア
Pass twice
2回通し
Emergency stop input and output etc. 3-90
3 Controller
Fig. 3-16
9
1A
+24V(COM)
34
1B
Input