Programming

3.6.12 Program Check

The Program Check feature allows the programmer to view the zones which have been
programmed to the Notification Appliance Circuits on the control panel but have not been
programmed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 3 while viewing Programming Screen #4 will cause the following screen to be displayed:
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
PROGRAMCHECK
Pressing 1 while viewing the Program Check screen will display an NAC screen similar to the
1=NACS NO INPUT
following.
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen
The example above indicates that NAC 1 has been programmed to Zones 05, 10, 12, 15 and 17 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for NAC 1 and NAC2.
136
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
NACS NO INPUT
NAC 1
05 10 12 15 17
MS-9050UD PN 52413:C 01/23/08