Programming
The programmer may hit the escape key and re-enter the password correctly. However, if the password has been forgotten, record the 20-
character code and contact Fire•Lite Technical Services. After proper authentication, the master password will be supplied to the pro-
grammer.
3.6.10 Clear Program
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Pressing 1, for Whole System while viewing the Clear Program Screen, will clear all general system programming options and all pro-
grammed addressable devices from the nonvolatile memory of the FACP. This function is useful when the control panel is first installed,
prior to autoprogramming. Note that it is necessary to autoprogram after using the Clear Whole System function.
Pressing 2, for All Points while viewing the Clear Program Screen, will clear all programming related to the SLC loop and connected
addressable devices.
Before executing any of the Clear commands listed above, the control panel will provide a warning to the user by prompting with the fol-
lowing display:
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will prevent programming from being cleared.
3.6.11 Program Check
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Pressing 1 while viewing the Program Check Screen will display an NAC screen similar to the following.
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but no input devices have been pro-
grammed to any of these zones. Use the up and down arrow keys to view all the NAC zones without input assignments for NAC 1,
NAC2, NAC 3 and NAC 4.
Pressing 2 while viewing the Program Check Screen #1 will display a screen similar to the following:
The Zone No Input screen allows the programmer to view the zones which have not been programmed to at least one input device (not
including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been pro-
grammed to an addressable module (control module in this example) with an address of 001 on loop 1 but have not been programmed to
any input devices. Use the up and down arrow keys to view all the zones without input assignments.
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
100
Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will cause the
LCD to display the following screen:
CLEAR PROGRAM
1=WHOLE SYSTEM
2=ALL POINTS
Clear Program Screen
WARNING!
SYSTEM CHANGE!
PROCEED?
1=YES
The Program Check feature allows the programmer to view the zones which have been programmed to the
Notification Appliance Circuits on the control panel but have not been programmed to Initiating Devices
as well as other circuits with no input or output correlations. Pressing 3 while viewing Programming
Screen #4 will cause the following screen to be displayed:
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
NACS NO INPUT
NAC 1
025 031 044 055 067
ZONES NO INPUT
005 007 009 010 011
1M001
Pressing 3 while viewing Program Check Screen #1 will cause a screen similar to the following to be dis-
played:
ZONES NO OUTPUT
005 007 009 010 011
1D001
2=NO
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Master Programming Level