Programming
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
PROGRAMCHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen
118
3.6.12 Program Check
The Program Check feature allows the programmer to view the zones which have been
programmed to the Notification Appliance Circuits on the control panel but have not
been programmed to Initiating Devices as well as other circuits with no input or output
correlations. Pressing 3 while viewing Programming Screen #4 will cause the
following screen to be displayed:
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Pressing 1 while viewing the Program Check screen will display an NAC screen similar
to the following.
NAC 1
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55
and 67 but no input devices have been programmed to any of these zones. Use the up
and down arrow keys to view all the NAC zones without input assignments for NAC 1,
NAC2, NAC 3 and NAC 4.
Note: If the NACs have been configured for Class A in the Setup option, only NAC1
and NAC 2 will display test information. NAC 3 and NAC 4 will display asterisks (*)
and will not be included in the test.
PROGRAMCHECK
NACS NO INPUT
25 31 44 55 67
MS-9200UDLS PN 52750:A 11/04/05
Master Programming Level