3.6.3.8 Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19
The display will show all of the zones that are still available for programming.
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 wiring and
to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the
following screen to be displayed:

1=STYLE

2=PROTOCOL
3.6.4.1 Style
To program the SLC Style for the loop, press 1 for Style, while viewing Loop Setup Screen. In
the preceding example, the control panel is programmed for Style 4 SLC wiring as indicated by
the 4 to the right of Style in the display. To change the style, press 1 to toggle the display to read
Style 6. Each press of the 1 key will cause the display to toggle between Style 4 and Style 6.
Note that, when programming the Loop Style, the programmer can only select between Style 4
and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop Setup
for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each device on
the loop must have a pair of isolator modules, one on each side. The factory default setting is
Style 4.
Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for
Style 6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired,
the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been
repaired) to clear the SLC trouble.

3.6.4.2 Loop Protocol

Loop Protocol refers to the SLC loop mode of operation. The only mode available is CLIP
(Classic Loop Interface Protocol) which is used for the older legacy addressable devices such as
the M300 Series modules and detectors as well as the newer devices. Pressing 2 while viewing
the Loop Setup Screen will have no effect on programming.
Device Addressing
It is important to note that the MS-9050UD addressable device capacity is 50 detectors and
control/monitor modules. Addressable devices must not be set to addresses higher than 50.
Programming will not allow addresses higher than 50.
Important: Detectors and Modules cannot have the same address. For example, if a detector is
installed at address 04, you cannot also have a module at address 04.
Note that It is permissible to mix old and new addressable devices on the same loop.
ZONES AVAILABLE
LOOP SETUP
Loop Setup Screen
4
CLIP
MS-9050UD PN 52413:C 01/23/08