Controls And Indicators - Honeywell Fire-Lite Alarms MS-5UD Series Manual

Fire alarm control panels
Table of Contents

Advertisement

Product Description

1.3 Controls and Indicators

LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
LED Indicators
LEDs are provided to annunciate the following conditions:
Fire Alarm - red LED
Supervisory - yellow LED
AC Power - green LED
System Trouble - yellow LED
Alarm Silence - yellow LED
Primary Phone Line Active (on circuit board) - red LED
Secondary Phone Line Active (on circuit board) - red LED
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process
monitor and supervisory conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse 1 second on and 1 second off
Supervisory - pulse ½ second on and ½ second off
Process Monitor - pulse ¼ second on and ¼ second off
20
SYSTEM ALL NORMAL
10:00A 012105
Figure 1.3 Membrane/Display Panel
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Controls and Indicators