Step 3 Check that the EPO alarm is cleared by viewing active alarms. If the system bypass
input is normal, the UPS transfers to bypass mode.
Step 4 Start the inverter.
----End

5.11 Exporting Data

The following data can be exported:
Web
1.
Issue 12 (2023-05-26)
On the LCD
On the LCD, choose System Info > Alarms and tap Clear Faults. In the
displayed dialog box, tap Yes. The EPO alarm is cleared successfully.
On the WebUI
Choose Monitoring > UPS system > Running Control > Issued Order and
click Clear Fault. The EPO alarm is cleared successfully.
On the old WebUI
Choose Monitoring > Control > System Commands and Tests and click
Clear Fault. The EPO alarm is cleared successfully.
Viewing active alarms on the LCD
Choose System Info > Alarms > Active Alarms to check that the EPO alarm
is cleared.
Viewing active alarms on the WebUI
Choose Home > Active Alarm to check that the EPO alarm is cleared.
Viewing active alarms on the old WebUI
Choose Monitoring > Active Alarms to check that the EPO alarm is cleared.
Historical Alarm
Active Alarms
Performance Data
Operation Log
E-Label
Fault Information
NO TE
This topic describes how to export historical alarms.
Choose Query > Export Data > Export Historical Data. Set Encryption
Password for Export, and select Historical Alarm from the Data Type drop-
down list.
Figure 5-21 Export Historical Data