Query - Huawei UPS5000-S-400K-SM User Manual

Hide thumbs Also See for UPS5000-S-400K-SM:
Table of Contents

Advertisement

UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
Thres. of low
batt. volt.
over dry
contact (V/
cell)
Battery String Summary
Item
No. of iBOX
iBAT start No.
iBAT end No.

4.2.4 Query

On the Query page, you can query Historical Alarm, Operation Log, and
Performance Data, and perform Export Data.
Figure 4-48 Query
Issue 12 (2023-05-26)
Description
Lead-acid battery: If an
output dry contact is set to
Batt. Volt. Below Threshold,
and the battery voltage is
lower than this threshold, the
output dry contact will
output signals.
Lithium battery: If Batt. Volt.
Below Threshold is set for
an output dry contact and
the minimum
electrochemical voltage is
lower than the threshold, the
output dry contact will
output signals.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Number of an iBOX connected to the UPS.
Start number of an iBAT connected to the iBOX.
End number of an iBAT connected to the iBOX.
4 User Interface
Default Value
Value Range
1.70
1.70–2.10
2.80
2.60–3.20
205

Advertisement

Table of Contents
loading

Table of Contents