UPS5000-S-(350 kVA-800 kVA)
User Manual
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0570-4
BPM module
abnormal
0583-1
Inter-rack par.
cable abnormal
0583-4
0583-5
0583-6
0584-2
Inter-rack par.
cable alarm
Issue 12 (2023-05-26)
Severity
Critical
Critical
Minor
Copyright © Huawei Digital Power Technologies Co., Ltd.
Cause
● The bypass fan
is not
functioning
properly, or the
air channel is
blocked.
● The ambient
temperature
exceeds the
upper
threshold.
● The load is
excessive.
● The inter-rack
parallel system
CAN bus is
disconnected
or short-
circuited.
● Only one rack
works in a
parallel system.
● An ECM is
faulty.
The inter-rack
industrial
frequency
synchronization
cable is broken.
The inter-rack
carrier
synchronization
cable is broken.
● The intra-rack
INVBYP cable is
broken.
● The parallel
CAN bus is
broken.
The inter-rack
parallel cable is
faulty.
B Alarm List
Solution
1. Check the bypass fan and
air channel. If the fan is
faulty, replace it.
2. Check that the ambient
temperature has not
exceeded 40°C.
3. Check that there is no
overload.
1. Check the inter-rack
parallel system CAN bus.
2. Rectify the disconnection
or short-circuit fault.
3. Replace the ECM.
Replace the inter-rack parallel
cable.
Replace the inter-rack parallel
cable.
288