UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
BSC mode
Altitude (m)
Top outlet fan Enable this parameter if a
Air filter
maintenance
period (d)
Issue 12 (2023-05-26)
Description
● Set this parameter to
Standard BSC for a dual-
bus system.
● After setting this
parameter to Standard
BSC, you need to set the
two UPS systems in the
dual-bus system to BSC
master system and BSC
slave system respectively
in the BSC master/slave
system setting. (The two
UPS systems cannot be
BSC master systems or
BSC slave systems at the
same time. If you need to
change the settings in the
future, perform operations
under the guidance of
maintenance engineers.)
NOTE
Ensure that the BSC signal cable
between the BSC master and
slave systems is properly
connected and that BSC-related
hardware is properly installed.
Set this parameter based on
the altitude of the place
where the rack is used.
top outlet fan is configured.
Then the fan running status
can be checked.
Specifies the rack air filter
maintenance interval. If it is
set to 0, there is no reminder.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Non-BSC
Non-BSC,
Standard BSC,
Optional BSC
card
≤ 1000
≤ 1000, 1000–
2000, 2000–
3000, 3000–
4000, 4000–
5000
Disable
Disable,
Enable
0
0–365
174