Huawei UPS5000-S-400K-SM User Manual page 81

Hide thumbs Also See for UPS5000-S-400K-SM:
Table of Contents

Advertisement

UPS5000-S-(350 kVA-800 kVA)
User Manual
When connecting power cables, comply with the tightening torque listed in
3-4
Table 3-4 Power cable connector requirements
Port
Mains
input
Bypass
input
Battery
input
Issue 12 (2023-05-26)
When selecting, connecting, and routing cables, follow local safety regulations
and rules.
If external conditions such as cable layout or ambient temperatures change,
perform verification in accordance with the IEC-60364-5-52 or local
regulations.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage
is 415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires by 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
The battery cable specifications are selected based on 40 batteries by default
and compatible with application scenarios with 30–50 batteries.
When the mains input and bypass input share a power source, configure
mains input power cables as input power cables. The cables listed in
3-2
and
Table 3-3
are used only when the following requirements are met:
Routing mode: The cables are routed over a tray or bracket in a single
layer (E in IEC 60364-5-52). The distance between cables should be
greater than twice the cable diameter.
Ambient temperature: 30°C
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%.
The 90°C flexible cables with copper conductors are used.
It is recommended that AC power cables be no longer than 30 meters
and DC power cables be no longer than 50 meters.
NO TICE
to ensure secure connections and prevent safety risks.
Connection
Mode
Crimped DT
terminals
Crimped DT
terminals
Crimped DT
terminals
Copyright © Huawei Digital Power Technologies Co., Ltd.
Bolt
Bolt Hole
Specifica
Diameter
tions
M16
18 mm
M16
18 mm
M16
18 mm
3 Installation
Table
Table
Bolt Length Torque
50 mm
120 N·m
50 mm
120 N·m
50 mm
120 N·m
72