Huawei UPS5000-S-400K-SM User Manual page 290

Hide thumbs Also See for UPS5000-S-400K-SM:
Table of Contents

Advertisement

UPS5000-S-(350 kVA-800 kVA)
User Manual
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0001-2
0001-3
0004-1
Mains ph.
Reversed
0005-1
Mains neutral
absent
0006-1
Mains
undervoltage
0010-1
Abnormal bypass
voltage
Issue 12 (2023-05-26)
Severity
Minor
Minor
Minor
Minor
Copyright © Huawei Digital Power Technologies Co., Ltd.
Cause
● Cable
connections
are incorrect.
● The mains is
not normal.
● The mains
input fuse for
the power
module is
blown.
The mains is not
normal.
Cable connections
are incorrect.
Cable connections
are incorrect.
● The mains is
not normal.
● The power
module
sampling
circuit is not
normal.
● The bypass
voltage range
is not correctly
set.
● The bypass
input voltage is
not normal.
B Alarm List
Solution
1. Check whether cables to
mains are disconnected,
loose, or incorrectly
connected.
2. If cable connections are
correct, measure the mains
voltage with a multimeter.
If the mains voltage is less
than 80 V, the mains
voltage is not normal; if
the mains voltage exceeds
88 V, the power module
sampling circuit or fuse
may not be working
properly. Replace the faulty
module.
Check the mains.
Verify the cable connections.
1. Secure or connect the
neutral wire to the cabinet
if it is loose or
disconnected.
2. Check that the neutral wire
to the power distribution
system is normal.
Check whether the mains
voltage ranges from 80 V
(excluding 80 V) to 176 V. If
no, the mains monitoring
circuit for the power module
is faulty. Replace the faulty
module.
1. Check the bypass input
voltage or cable
connections with a
multimeter.
2. Check the voltage system
and bypass voltage
thresholds configured on
the LCD.
281