UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
D.G. mode
D.G. power
limiting (kVA)
D.G. charger
power ratio
(%)
Input cur.
limiting
Input cur.
limiting ratio
(%)
Output Settings
Figure 4-26 Output settings
Issue 12 (2023-05-26)
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters
the D.G. mode when a D.G. is
detected over dry contacts.
Set these two parameters to
control the valid input
current and limiting input
current, which prevents load
impact and facilitates better
cooperation between the
UPS and the D.G.
Specifies whether to enable
or disable input current
limiting to protect
generators.
Limits the input current to
protect the D.G.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable,
Enable
Depends on
0–5000
the actual
model.
100
0–100
Disable
Disable,
Enable
200
50–200
176