UPS5000-S-(350 kVA-800 kVA)
User Manual
Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS
discharge time. When you set battery parameters, note the following:
● Battery string sharing is unavailable when Single/Parallel is set as Single.
● Battery string sharing affects the actual charge current and the estimated
● When you set parameters, ensure the following: Dis. cur. 0.1C EOD ≥ Dis. cur.
● A cell consists of electrodes and electrolyte, which is the basic unit for the
Figure 4-28 Battery settings (lead-acid battery)
Figure 4-29 Battery settings (lithium battery)
Item
Battery type
Issue 12 (2023-05-26)
NO TICE
discharge time. An incorrect setting will cause a high or low charge current,
which may damage the batteries. An incorrect estimated discharge time may
cause a data backup fault.
0.3C EOD ≥ Dis. cur. 0.5C EOD ≥ Dis. cur. 1.0C EOD.
battery. Each cell has a nominal voltage of 2 V. A battery is a module consisting
of single or multiple cells in a shell. Each battery has a nominal voltage of 2 V,
6 V, or 12 V.
Description
Type of batteries connected
to the UPS.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
VRLA batt.
VRLA batt.,
lithium batt.
180