UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
Sched.
shallow dis.
test
Sched.
shallow dis.
test time
Sched.
shallow dis.
test interval
(d)
Shallow dis.
test dis. ratio
(%)
Cell charge
voltage (V/
cell)
Chg. cur.
limiting coef.
(C)
Issue 12 (2023-05-26)
Description
When certain conditions are
met, the charger shuts down,
and batteries supply power to
loads. The system records the
battery discharge data as the
reference for battery capacity
and lifespan.
Time for scheduled shallow
discharge test.
Interval for scheduled
shallow discharge test.
Set the proportion of the
discharge capacity to the
total discharge capacity. The
value is configurable in any
mode.
Charge voltage of lithium
batteries (the value is
automatically obtained)
Lithium battery: The charging
current limit is a multiple of
the battery capacity.
Lead-acid battery: The
charging current limit is a
multiple of the battery
capacity.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable,
Enable
00:00 - 06:00
00:00 - 06:00,
06:00 - 12:00,
12:00 - 18:00,
18:00 - 24:00
60
30–90
20
10–50
N/A
N/A
0.50
0.10–1.00
0.10
0.05–0.15
182