UPS5000-S-(350 kVA-800 kVA)
User Manual
Issue 12 (2023-05-26)
Figure 4-69 RCCMD message
RCCMD Execute: Specify the RCCMD client IP address, port, and command to
be executed. For example, enter SHUTDOWN, and the RCCMD client will shut
down the computer after receiving the command.
Figure 4-70 RCCMD execute
RCCMD TRAP: When the event happens, the MDU will send the TRAP
message to all connected RCCMD clients based on the sending mechanism.
If you want to define the TRAP message by yourself, you can use the TRAP
signal to display the UPS information. For example, if you enter #INVOLT V,
the RCCMD client will receive the UPS input voltage value (for example,
single-phase: 220 V; three-phase A: 220 V, B: 220 V, C: 220 V).
the signal names that can be entered.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Table 4-23
lists
231