UPS5000-S-(350 kVA-800 kVA)
User Manual
Procedure
Step 1 Manually switch the UPS to bypass mode.
Step 2 Turn on the maintenance bypass switch.
If the maintenance bypass switch is locked, unlock it first.
5-17
maintenance bypass switch, the UPS transfers to maintenance bypass mode. The
maintenance bypass switch is OFF by default. To turn on the maintenance bypass
switch, rotate it to the ON position, as shown in
Figure 5-16 Locked maintenance bypass switch (400 kVA UPS and 500 kVA UPS)
Figure 5-17 Locked maintenance bypass switch (600 kVA UPS)
Figure 5-18 Turning on the maintenance bypass switch (400 kVA UPS in full
configuration)
Issue 12 (2023-05-26)
show a locked maintenance bypass switch. After you turn on the
Copyright © Huawei Digital Power Technologies Co., Ltd.
Figure 5-16
Figure 5-18
and
Figure
5 Operations
and
Figure
5-19.
256