UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
Battery
capacity (Ah)
Single battery
voltage (V)
Single battery
capacity (Ah)
Batteries in a
battery string
Number of
battery
strings
Installation
time
Maintenance
period (d)
Cell float
voltage (V/
cell)
Cell equalized
volt. (V/cell)
Dis. cur. 0.1C
EOD (V/cell)
Dis. cur. 0.3C
EOD (V/cell)
Dis. cur. 0.5C
EOD (V/cell)
Dis. cur. 1.0C
EOD (V/cell)
Issue 12 (2023-05-26)
Description
Capacity of lithium batteries
connected to the UPS (the
value is automatically
obtained).
Specifies the voltage of each
battery that is connected in
the battery string in series.
Specifies the capacity of each
battery that is connected in
the battery string in series.
Specifies the number of
batteries in a battery string.
Specifies the number of
battery strings connected in
parallel.
A battery maintenance
reminder is displayed when
the maintenance time
(counted from the
installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
Specifies the battery float
charging voltage.
Specifies the battery
equalized charging voltage.
Specifies the EOD threshold
when the discharging current
is 0.1C, 0.3C, 0.5C, and 1.0C
respectively.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
-
-
12
2, 6, 12
Depends on
5–9999
the actual
model.
The default
The value
value depends
range depends
on the model.
on the model.
1
1–6
N/A
N/A
0
0–365
2.25
2.23–2.30
2.35
2.30–2.40
1.80
1.80–1.90
1.80
1.80–1.90
1.75
1.75–1.85
1.60
1.60–1.75
181