Huawei UPS5000-S-400K-SM User Manual page 226

Hide thumbs Also See for UPS5000-S-400K-SM:
Table of Contents

Advertisement

UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
Bus overvolt.
recovery time
Capacitor
failure
detection
Bypass Settings
Item
BPM mode
upon BPM
overtemp.
Issue 12 (2023-05-26)
Description
If Bus overvoltage recovery
is set to Enable, the bus
overvoltage alarm is
automatically cleared, and
the rectifier and inverter
automatically start when the
bus voltage recovers (less
than 420 V) within Bus
overvolt. recovery time.
If Capacitor failure
detection is set to Enable,
the power module (power
unit) performs inverter
capacitor fault detection
based on the settings of
Capacitor failure detection
upper limit and Capacitor
failure detection lower
limit. If the power module
determines that the inverter
capacitor is faulty, it shuts
down the inverter to prevent
the fault from expanding.
Description
Specifies whether to start
bypass mode when
overtemperature occurs.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
5s
5s, 1 min, 5
min, 10 min
Disable
Disable,
Enable
Default Value
Value Range
Enable
Disable,
Enable
217