Huawei UPS5000-S-400K-SM User Manual page 213

Hide thumbs Also See for UPS5000-S-400K-SM:
Table of Contents

Advertisement

UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
Batt. charging
capacity
mismatch
Batt. mode
shut
Bat mode
shut delay (s)
Backup time
warning
Backup time
warning
thresh. (min)
Remain. cap.
warning
Remain. cap.
warn. thresh.
(%)
Intelligent
hibernation
Class 1 grid
hiber. time
(d)
Class 2 grid
hiber. time
(d)
Thres. of low
batt. SOC
over dry
contact (%)
Issue 12 (2023-05-26)
Description
After this function is enabled,
an alarm is generated if the
configured battery capacity
exceeds the charging
capacity of the rack.
In battery mode, the UPS can
automatically power off
according to the preset
shutdown delay time. If the
parameter is disabled, this
function is not available.
Shutdown delay in battery
mode.
An alarm is generated if this
parameter is set to Enable
and the backup time is less
than the warning threshold.
Backup time warning
threshold.
An alarm is generated if this
parameter is set to Enable
and the remaining capacity is
less than the warning
threshold.
Remaining capacity warning
threshold
If this parameter is set to
Enable, the intelligent
battery hibernation function
is enabled.
Hibernation time for class 1
power grids.
Hibernation time for class 2
power grids.
If an output dry contact is set
to Low battery SOC, and the
battery SOC is lower than
this threshold, the output dry
contact will output signals.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable,
Enable
Disable
Disable,
Enable
7200
0–7200
Disable
Disable,
Enable
5
3 to 30
Disable
Disable,
Enable
20
5–50
Disable
Disable,
Enable
13
0–30
6
0–15
75
5–80
204