Huawei UPS5000-S-400K-SM User Manual page 187

Hide thumbs Also See for UPS5000-S-400K-SM:
Table of Contents

Advertisement

UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
EOD restart
EOD restart
delay (min)
Bypass Settings
Figure 4-27 Bypass settings
Issue 12 (2023-05-26)
Description
If the mains is not
functioning normally, the
UPS will transfer to battery
mode. When batteries reach
the EOD threshold, the
bypass is disabled, and EOD
restart is Enable, the UPS
will restart as soon as the
mains resumes.
If EOD restart is disabled,
clear the alarm manually or
enable the restart function
for the UPS.
If EOD restart is set to
Enable, the UPS starts
working after the time set for
EOD restart delay when the
input recovers from the
power failure upon EOD.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable,
Enable
10
1–1440
178