UPS5000-S-(350 kVA-800 kVA)
User Manual
Item
Intra-rack
power
module start
delay (s)
Inter-rack
power
module start
delay (s)
Batt. temp.
sensor
[B_TEMP]
NTC
BCB trips if
UPS stops
power supply
Input Settings
Figure 4-25 Input settings
Issue 12 (2023-05-26)
Description
These two parameters enable
the UPS to control the
interval that each rack (or
module) transfers from
battery mode to normal
mode, which reduces the
impact on the generator or
power grid. In the case of
battery undervoltage, the
system automatically
shortens the delay for
transferring to normal mode
to 1/8 of the normal delay to
accelerate the transfer and
prevent battery
overdischarge. The start
delay of a module in a rack
varies depending on the rack
number and module number.
#1 module in rack 1 does not
have a start delay.
The short-distance battery
temperature sensor monitors
the ambient temperature
near batteries, and ensures
that batteries work reliably
and securely.
Indicates whether the BCB
trips when the system stops
supplying power and the
output power is off.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
The default
0.5–120.0
value of this
parameter
depends on
the default
number of
power
modules. The
default value
is 2.0, 1.0, and
0.5 for 1–5, 6–
10, and 10–20
power
modules
respectively.
5
2–120
Disable
Disable,
Enable
Enable
Disable,
Enable
175