Huawei UPS5000-S-400K-SM User Manual page 83

Hide thumbs Also See for UPS5000-S-400K-SM:
Table of Contents

Advertisement

UPS5000-S-(350 kVA-800 kVA)
User Manual
UPS Capacity
600 kVA
650 kVA
700 kVA
750 kVA
800 kVA
a: Circuit breakers configured for the 400 kVA UPS are used in circuits with a
short-circuit current of less than 35 kA, and those for the 500/600/800 kVA UPS
are used in circuits with a short-circuit current of less than 50 kA.
Issue 12 (2023-05-26)
Component Name
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Copyright © Huawei Digital Power Technologies Co., Ltd.
a
Specifications
1000 A/3P
1250 A/3P
1000 A/3P
1000 A/3P
1600 A/3P
1000 A/3P
1000 A/3P
1600 A/3P
1250 A/3P
1250 A/3P
1600 A/3P
1250 A/3P
1250 A/3P
1600 A/3P
1250 A/3P
1250 A/3P
3 Installation
74